PSU & PMBus Management

Monitor power supplies through the PMBus protocol, from kernel hwmon interfaces through D-Bus sensors to Redfish telemetry.

Table of Contents

  1. Overview
  2. Architecture
    1. PSU Monitoring Data Flow
    2. D-Bus Interfaces
    3. Key Repositories
  3. Configuration
    1. PMBus Sysfs Interface
    2. Device Tree Configuration
    3. Verify Kernel Driver Binding
    4. Entity Manager PSU Configuration
    5. Voltage Regulator Configuration (phosphor-regulators)
    6. Build-Time Configuration (Yocto)
    7. Deploy Configuration via Yocto bbappend
      1. Entity Manager PSU Config
      2. Regulators Config
  4. Porting Guide
    1. Step 1: Identify PSU Hardware
    2. Step 2: Add Device Tree Entries
    3. Step 3: Verify Kernel Binding
    4. Step 4: Create Entity Manager JSON
    5. Step 5: Add Yocto bbappend Files
    6. Step 6: Verify End-to-End
  5. Code Examples
    1. Reading PSU Sensors from D-Bus
    2. Querying PSU Inventory via D-Bus
    3. Querying PSU Data via Redfish
  6. Troubleshooting
    1. PSU Not Detected on I2C
    2. No Sensors Appearing on D-Bus
    3. Incorrect Sensor Readings
    4. PSU Fault Detected
    5. Regulators Service Fails to Start
    6. PSU Threshold Alarms Not Triggering
  7. References

Overview

Power Supply Units (PSUs) in server platforms communicate over the PMBus protocol, an I2C-based standard for power device management. OpenBMC provides a full monitoring pipeline that reads PMBus telemetry from hardware and exposes it through standardized interfaces for out-of-band management.

The pipeline flows through five layers:

  1. PMBus hardware – the PSU responds to I2C commands defined by the PMBus specification
  2. Linux hwmon – the kernel pmbus driver translates PMBus registers into sysfs attributes
  3. phosphor-power / dbus-sensors – userspace daemons read hwmon and publish D-Bus sensor objects
  4. D-Bus – the common bus where all OpenBMC services exchange sensor data and inventory
  5. Redfish / IPMI – northbound interfaces that expose PSU data to remote management tools

This guide covers the complete workflow: configuring the kernel driver, writing Entity Manager JSON for PSU discovery, setting up phosphor-regulators for voltage regulator control, reading sensor data through D-Bus and Redfish, and troubleshooting common issues.

PSU monitoring is partially testable in QEMU. The ast2600-evb QEMU target emulates I2C buses, but real PMBus device responses require physical hardware or a PMBus simulator connected to the I2C bus.


Architecture

PSU Monitoring Data Flow

PSU (PMBus Device on I2C Bus)
        |
        v
Linux Kernel: pmbus driver
  /sys/class/hwmon/hwmonN/
  ├── in1_input    (input voltage)
  ├── in2_input    (output voltage)
  ├── curr1_input  (input current)
  ├── curr2_input  (output current)
  ├── power1_input (input power)
  ├── power2_input (output power)
  ├── temp1_input  (hotspot temp)
  └── fan1_input   (internal fan RPM)
        |
        v
Userspace Daemons
  ├── PSUSensor (dbus-sensors)     -- reads hwmon, publishes sensors
  ├── phosphor-psu-monitor         -- PSU presence, faults, inventory
  └── phosphor-regulators          -- VR config and rail monitoring
        |
        v
D-Bus
  ├── xyz.openbmc_project.Sensor.Value        (telemetry)
  ├── xyz.openbmc_project.Inventory.Item      (presence)
  ├── xyz.openbmc_project.State.Decorator.OperationalStatus (health)
  └── xyz.openbmc_project.Inventory.Decorator.Asset (FRU data)
        |
        v
Northbound Interfaces
  ├── bmcweb (Redfish)  --> /redfish/v1/Chassis/chassis/Power
  └── ipmid  (IPMI)    --> SDR / SEL entries

D-Bus Interfaces

Interface Object Path Description
xyz.openbmc_project.Sensor.Value /xyz/openbmc_project/sensors/voltage/PSU0_Input_Voltage Voltage, current, power, temperature readings
xyz.openbmc_project.Inventory.Item /xyz/openbmc_project/inventory/system/chassis/powersupply0 PSU presence and identity
xyz.openbmc_project.Inventory.Decorator.Asset /xyz/openbmc_project/inventory/system/chassis/powersupply0 Manufacturer, model, serial number
xyz.openbmc_project.State.Decorator.OperationalStatus /xyz/openbmc_project/inventory/system/chassis/powersupply0 Functional status (true/false)

Key Repositories

Repository Component Description
phosphor-power phosphor-power-supply/ PSU monitoring daemon
phosphor-power phosphor-regulators/ Voltage regulator configuration and control
dbus-sensors src/PSUSensor.cpp PSU sensor daemon (reads hwmon, publishes D-Bus)
entity-manager JSON configs PSU hardware discovery and configuration

Configuration

PMBus Sysfs Interface

When the kernel pmbus driver binds to a PSU, it creates hwmon attributes under /sys/class/hwmon/hwmonN/. The following table lists the most common attributes and their corresponding PMBus registers.

Sysfs Attribute PMBus Command Code Description Unit
in1_input READ_VIN 0x88 Input voltage millivolts
in2_input READ_VOUT 0x8B Output voltage millivolts
curr1_input READ_IIN 0x89 Input current milliamps
curr2_input READ_IOUT 0x8C Output current milliamps
power1_input READ_PIN 0x97 Input power microwatts
power2_input READ_POUT 0x96 Output power microwatts
temp1_input READ_TEMPERATURE_1 0x8D Temperature sensor 1 millidegrees C
temp2_input READ_TEMPERATURE_2 0x8E Temperature sensor 2 millidegrees C
fan1_input READ_FAN_SPEED_1 0x90 Fan speed RPM

The PMBus STATUS_WORD register (0x79) provides a summary of all fault conditions:

# Read STATUS_WORD directly from I2C
i2cget -y 3 0x58 0x79 w

# Bit definitions (STATUS_WORD, 16-bit):
#   Bit 15: VOUT fault or warning
#   Bit 14: IOUT/POUT fault or warning
#   Bit 13: INPUT fault or warning
#   Bit 12: MFR specific fault
#   Bit 11: POWER_GOOD negated
#   Bit  6: OFF (unit not providing power)
#   Bit  5: FANS fault or warning
#   Bit  4: OTHER (reserved)
#   Bit  3: VIN_UV fault
#   Bit  2: TEMPERATURE fault or warning
#   Bit  1: CML (communication/logic fault)
#   Bit  0: None of the above

Use i2cget and i2cdump to verify PMBus communication before configuring the monitoring stack. If raw I2C reads fail, the PSU address may be wrong or the I2C bus is not enabled in the device tree.

Device Tree Configuration

Declare the PSU on its I2C bus in the device tree so the kernel pmbus driver binds automatically at boot:

&i2c3 {
    status = "okay";

    psu0: psu@58 {
        compatible = "pmbus";
        reg = <0x58>;
    };

    psu1: psu@59 {
        compatible = "pmbus";
        reg = <0x59>;
    };
};

If your PSU has a vendor-specific driver (for example, ibm,cffps or delta,dps800), use the vendor compatible string instead of generic "pmbus". Vendor drivers expose additional attributes such as firmware version and detailed fault registers.

Verify Kernel Driver Binding

# Check the I2C bus for devices
i2cdetect -y 3

# Verify the pmbus driver bound
ls /sys/bus/i2c/devices/3-0058/driver
# Should show symlink to pmbus or vendor driver

# Find the hwmon path
ls /sys/bus/i2c/devices/3-0058/hwmon/
# hwmon5

# Read input voltage (millivolts)
cat /sys/class/hwmon/hwmon5/in1_input
# 229800  (229.8 V)

# Read output power (microwatts)
cat /sys/class/hwmon/hwmon5/power2_input
# 245000000  (245 W)

Entity Manager PSU Configuration

Entity Manager discovers PSUs and publishes their configuration on D-Bus so that sensor daemons know which devices to monitor. Create a JSON configuration file for your platform.

File: /usr/share/entity-manager/configurations/my-platform-psu.json

{
    "Name": "PSU0",
    "Type": "Board",
    "Probe": "xyz.openbmc_project.FruDevice({'PRODUCT_PRODUCT_NAME': 'MyPSU-1200W'})",

    "Exposes": [
        {
            "Name": "PSU0",
            "Type": "pmbus",
            "Bus": 3,
            "Address": "0x58",
            "Labels": [
                "vin",
                "vout1",
                "iin",
                "iout1",
                "pin",
                "pout1",
                "temp1",
                "temp2",
                "fan1"
            ],
            "Thresholds": [
                {
                    "Direction": "greater than",
                    "Label": "temp1",
                    "Name": "upper critical",
                    "Severity": 1,
                    "Value": 100
                },
                {
                    "Direction": "greater than",
                    "Label": "temp1",
                    "Name": "upper warning",
                    "Severity": 0,
                    "Value": 85
                },
                {
                    "Direction": "less than",
                    "Label": "vin",
                    "Name": "lower critical",
                    "Severity": 1,
                    "Value": 180
                },
                {
                    "Direction": "less than",
                    "Label": "vin",
                    "Name": "lower warning",
                    "Severity": 0,
                    "Value": 200
                }
            ]
        }
    ],

    "xyz.openbmc_project.Inventory.Item": {
        "Present": true,
        "PrettyName": "Power Supply 0"
    },

    "xyz.openbmc_project.Inventory.Decorator.Asset": {
        "Manufacturer": "$PRODUCT_MANUFACTURER",
        "Model": "$PRODUCT_PRODUCT_NAME",
        "SerialNumber": "$PRODUCT_SERIAL_NUMBER"
    }
}

Key fields:

Field Description
Probe Matches against FRU data to detect PSU presence. Use "TRUE" for always-present PSUs.
Type (in Exposes) Set to "pmbus" so PSUSensor daemon claims this device.
Bus / Address I2C bus number and 7-bit hex address of the PSU.
Labels Which PMBus sensor channels to expose. Maps to hwmon attribute names.
Thresholds Warning and critical limits for alarm generation.
$PRODUCT_* Entity Manager substitutes these from FRU EEPROM data at runtime.

The Labels array controls which sensors appear on D-Bus. If you omit a label, PSUSensor will not create a sensor for that channel even if the hwmon attribute exists. Always verify which labels your PSU actually supports by checking the hwmon sysfs attributes.

Voltage Regulator Configuration (phosphor-regulators)

phosphor-regulators manages on-board voltage regulators (VRMs) that use PMBus for control. It reads a JSON configuration file to set output voltages during power-on and monitor rail health during operation.

File: /usr/share/phosphor-regulators/config.json

{
    "rules": [
        {
            "id": "set_voltage_rule",
            "actions": [
                {
                    "pmbus_write_vout_command": {
                        "format": "linear",
                        "exponent": -8
                    }
                }
            ]
        },
        {
            "id": "read_sensors_rule",
            "actions": [
                {
                    "pmbus_read_sensor": {
                        "type": "vout",
                        "command": "0x8B",
                        "format": "linear_16"
                    }
                },
                {
                    "pmbus_read_sensor": {
                        "type": "iout",
                        "command": "0x8C",
                        "format": "linear_11"
                    }
                },
                {
                    "pmbus_read_sensor": {
                        "type": "temperature",
                        "command": "0x8D",
                        "format": "linear_11"
                    }
                }
            ]
        }
    ],
    "chassis": [
        {
            "number": 1,
            "inventory_path": "/xyz/openbmc_project/inventory/system/chassis",
            "devices": [
                {
                    "id": "vdd_cpu0",
                    "is_regulator": true,
                    "fru": "/xyz/openbmc_project/inventory/system/chassis/motherboard/cpu0",
                    "i2c_interface": {
                        "bus": 5,
                        "address": "0x40"
                    },
                    "presence_detection": {
                        "rule_id": "detect_presence_rule"
                    },
                    "configuration": {
                        "volts": 1.0,
                        "rule_id": "set_voltage_rule"
                    },
                    "rails": [
                        {
                            "id": "vdd_cpu0_rail",
                            "sensor_monitoring": {
                                "rule_id": "read_sensors_rule"
                            }
                        }
                    ]
                }
            ]
        }
    ]
}

Configuration sections:

Section Purpose
rules Reusable action sequences for reading sensors or writing voltage commands.
chassis Top-level grouping that maps to a physical chassis in inventory.
devices Individual voltage regulators with I2C bus/address and FRU path.
configuration Voltage set point and rule to apply during power-on.
rails Output rails to monitor; each rail can have sensor monitoring rules.

The format field in pmbus_read_sensor specifies how to decode the PMBus register. Use linear_11 for current, power, and temperature readings (11-bit mantissa, 5-bit exponent). Use linear_16 for VOUT readings (16-bit mantissa with exponent from VOUT_MODE register).

Build-Time Configuration (Yocto)

Include the PSU monitoring components in your image:

# In your machine .conf or image recipe

# PSU sensor daemon (from dbus-sensors)
IMAGE_INSTALL:append = " psusensor"

# PSU monitoring and inventory (from phosphor-power)
IMAGE_INSTALL:append = " \
    phosphor-power-psu-monitor \
    phosphor-power-regulators \
    phosphor-power-utils \
"

Deploy Configuration via Yocto bbappend

Entity Manager PSU Config

# meta-myplatform/recipes-phosphor/configuration/entity-manager/
# +-- files/
# |   +-- my-platform-psu.json
# +-- entity-manager_%.bbappend

cat > entity-manager_%.bbappend << 'EOF'
FILESEXTRAPATHS:prepend := "${THISDIR}/files:"
SRC_URI += "file://my-platform-psu.json"

do_install:append() {
    install -d ${D}${datadir}/entity-manager/configurations
    install -m 0444 ${WORKDIR}/my-platform-psu.json \
        ${D}${datadir}/entity-manager/configurations/
}
EOF

Regulators Config

# meta-myplatform/recipes-phosphor/power/phosphor-regulators/
# +-- files/
# |   +-- my-regulators-config.json
# +-- phosphor-regulators_%.bbappend

cat > phosphor-regulators_%.bbappend << 'EOF'
FILESEXTRAPATHS:prepend := "${THISDIR}/files:"
SRC_URI += "file://my-regulators-config.json"

do_install:append() {
    install -d ${D}${datadir}/phosphor-regulators
    install -m 0644 ${WORKDIR}/my-regulators-config.json \
        ${D}${datadir}/phosphor-regulators/config.json
}
EOF

Porting Guide

Follow these steps to bring up PSU monitoring on a new platform.

Step 1: Identify PSU Hardware

Determine the following from your platform schematic:

Parameter Example How to find
I2C bus number 3 Schematic, trace from BMC I2C controller to PSU connector
PSU I2C address 0x58 PSU datasheet or i2cdetect -y <bus>
Number of PSUs 2 Platform design (N+1 redundancy)
PMBus commands supported See datasheet PSU vendor documentation
Vendor-specific driver "delta,dps800" Kernel driver list or "pmbus" for generic

Step 2: Add Device Tree Entries

// In your platform device tree (aspeed-bmc-myplatform.dts)
&i2c3 {
    status = "okay";

    psu0: psu@58 {
        compatible = "pmbus";
        reg = <0x58>;
    };

    psu1: psu@59 {
        compatible = "pmbus";
        reg = <0x59>;
    };
};

Step 3: Verify Kernel Binding

After booting with the updated device tree:

# Confirm devices appear on the bus
i2cdetect -y 3

# Verify driver bound
ls /sys/bus/i2c/devices/3-0058/driver

# List hwmon attributes to determine which Labels to use
ls /sys/bus/i2c/devices/3-0058/hwmon/hwmon*/
# in1_input  in2_input  curr1_input  curr2_input
# power1_input  power2_input  temp1_input  fan1_input

Step 4: Create Entity Manager JSON

Map each hwmon attribute to a Label in your JSON configuration. Only include labels that exist in sysfs.

Step 5: Add Yocto bbappend Files

Install your Entity Manager JSON and, if applicable, your phosphor-regulators config through bbappend files as shown in the Configuration section.

Step 6: Verify End-to-End

# Check Entity Manager detected the PSU
busctl tree xyz.openbmc_project.EntityManager | grep -i psu

# Verify PSU sensors on D-Bus
busctl tree xyz.openbmc_project.PSUSensor

# Read a sensor value
busctl get-property xyz.openbmc_project.PSUSensor \
    /xyz/openbmc_project/sensors/voltage/PSU0_Input_Voltage \
    xyz.openbmc_project.Sensor.Value Value

# Check via Redfish
curl -k -u root:0penBmc \
    https://localhost:2443/redfish/v1/Chassis/chassis/Power

Code Examples

Working examples are available in the examples/psu-pmbus directory:

  • psu-entity-manager.json – Entity Manager configuration for a dual-PSU platform
  • regulators-config.json – phosphor-regulators configuration with VRM rules
  • psu-status-check.sh – Shell script to read PMBus STATUS_WORD and decode fault bits

Reading PSU Sensors from D-Bus

#!/bin/bash
# Read all PSU sensors and display a summary

PSU_SERVICE="xyz.openbmc_project.PSUSensor"
SENSOR_BASE="/xyz/openbmc_project/sensors"

echo "=== PSU Sensor Readings ==="

for type in voltage current power temperature; do
    echo ""
    echo "--- ${type} ---"
    busctl tree ${PSU_SERVICE} 2>/dev/null \
        | grep "${type}" \
        | while read -r path; do
            value=$(busctl get-property ${PSU_SERVICE} \
                "${path}" \
                xyz.openbmc_project.Sensor.Value Value 2>/dev/null \
                | awk '{print $2}')
            name=$(basename "${path}")
            echo "  ${name}: ${value}"
        done
done

Querying PSU Inventory via D-Bus

# List PSU inventory objects
busctl tree xyz.openbmc_project.Inventory.Manager | grep powersupply

# Get PSU presence
busctl get-property xyz.openbmc_project.Inventory.Manager \
    /xyz/openbmc_project/inventory/system/chassis/powersupply0 \
    xyz.openbmc_project.Inventory.Item Present

# Get PSU asset information (manufacturer, model, serial)
busctl get-property xyz.openbmc_project.Inventory.Manager \
    /xyz/openbmc_project/inventory/system/chassis/powersupply0 \
    xyz.openbmc_project.Inventory.Decorator.Asset Manufacturer

busctl get-property xyz.openbmc_project.Inventory.Manager \
    /xyz/openbmc_project/inventory/system/chassis/powersupply0 \
    xyz.openbmc_project.Inventory.Decorator.Asset SerialNumber

Querying PSU Data via Redfish

# Get power supply collection
curl -k -u root:0penBmc \
    https://localhost:2443/redfish/v1/Chassis/chassis/Power \
    | jq '.PowerSupplies'

# Get specific sensor reading
curl -k -u root:0penBmc \
    https://localhost:2443/redfish/v1/Chassis/chassis/Sensors/PSU0_Input_Voltage

# Get power supply inventory with FRU data
curl -k -u root:0penBmc \
    https://localhost:2443/redfish/v1/Chassis/chassis/Power \
    | jq '.PowerSupplies[] | {Name, Model, Manufacturer, SerialNumber, Status}'

Troubleshooting

PSU Not Detected on I2C

# Scan the I2C bus
i2cdetect -y 3
# If address 0x58 shows "--", the PSU is not responding

# Check device tree
cat /sys/firmware/devicetree/base/ahb/apb/bus@1e78a000/i2c-bus@180/psu@58/compatible

# Try reading MFR_ID to confirm PMBus communication
i2cget -y 3 0x58 0x99 s   # MFR_ID (block read)
i2cget -y 3 0x58 0x79 w   # STATUS_WORD

If i2cdetect shows the address but the pmbus driver does not bind, you may need to manually instantiate the device: echo pmbus 0x58 > /sys/bus/i2c/devices/i2c-3/new_device

No Sensors Appearing on D-Bus

# Check PSUSensor daemon status
systemctl status xyz.openbmc_project.psusensor
journalctl -u xyz.openbmc_project.psusensor -f

# Check Entity Manager found the PSU configuration
journalctl -u xyz.openbmc_project.EntityManager | grep -i psu

# Verify the hwmon sysfs path exists
ls /sys/bus/i2c/devices/3-0058/hwmon/

# Check if Labels in Entity Manager config match actual hwmon attributes
ls /sys/bus/i2c/devices/3-0058/hwmon/hwmon*/

A common failure is mismatched Labels. If your Entity Manager config lists "vout1" but the hwmon driver only creates in2_input (without a label file), PSUSensor may not find the sensor. Check the hwmon attribute names and adjust Labels accordingly.

Incorrect Sensor Readings

# Compare D-Bus value with raw hwmon value
cat /sys/class/hwmon/hwmon5/in1_input
# 229800 (millivolts = 229.8 V)

busctl get-property xyz.openbmc_project.PSUSensor \
    /xyz/openbmc_project/sensors/voltage/PSU0_Input_Voltage \
    xyz.openbmc_project.Sensor.Value Value
# d 229.8

# If values differ, check for scaling issues in the kernel driver
# or Entity Manager ScaleFactor/Offset properties

PSU Fault Detected

# Read STATUS_WORD to identify the fault type
i2cget -y 3 0x58 0x79 w

# Decode individual status registers for details
i2cget -y 3 0x58 0x7A b   # STATUS_VOUT
i2cget -y 3 0x58 0x7B b   # STATUS_IOUT
i2cget -y 3 0x58 0x7C b   # STATUS_INPUT
i2cget -y 3 0x58 0x7D b   # STATUS_TEMPERATURE
i2cget -y 3 0x58 0x81 b   # STATUS_FANS_1_2

# Clear faults after resolving the issue
i2cset -y 3 0x58 0x03     # CLEAR_FAULTS command

# Check PSU operational status on D-Bus
busctl get-property xyz.openbmc_project.Inventory.Manager \
    /xyz/openbmc_project/inventory/system/chassis/powersupply0 \
    xyz.openbmc_project.State.Decorator.OperationalStatus Functional

Regulators Service Fails to Start

# Check service status
systemctl status phosphor-regulators
journalctl -u phosphor-regulators --no-pager | tail -30

# Validate JSON configuration syntax
python3 -m json.tool /usr/share/phosphor-regulators/config.json > /dev/null

# Common issues:
# - Invalid I2C bus/address in config (device not present)
# - Missing rule_id reference (typo in rule name)
# - Incorrect PMBus format (linear_11 vs linear_16)

PSU Threshold Alarms Not Triggering

# Verify thresholds are set on D-Bus
busctl introspect xyz.openbmc_project.PSUSensor \
    /xyz/openbmc_project/sensors/temperature/PSU0_Temperature_1 \
    | grep -i threshold

# Check that sel-logger is running (required for SEL entries)
systemctl status xyz.openbmc_project.sel-logger

# Monitor threshold events in real time
journalctl -u xyz.openbmc_project.sel-logger -f | grep -i threshold

References


Tested on: OpenBMC master, QEMU ast2600-evb (I2C bus enumeration verified; full PMBus telemetry requires physical PSU hardware)


Back to top